Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Routine |
Inspection date: | December 08, 2006 |
Follow-up Required: | Yes |
This facility was given a high hazard rating.
More information on hazard ratings.
Chlorine (Total) 3.0ppm |
Chlorine (Free Available) 1.5ppm |
Chlorine (Combined) |
Bromine (Free Available) |
pH 7.8 |
Total Alkalinity 130ppm |
Total Hardness |
Temperature |
Clarity Good |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
413 | Critical Other (specify below) Observation: Concentration of combined chlorines is measured to be 1.0 - 1.5ppm. Concentration of combined chlorines is to be maintained below 1.0ppm. Corrective Action: Pool is to be closed until it can be verified that the concentration of combined chlorines is less than 1.0ppm. Shock chlorinate the pool. |
413 | Critical Other (specify below) Observation: Flow meter for the pool is not functional. Corrective Action: Repair/replace flow meter. |
421 | Repeat Other (specify below) Observation: A sample of pool water was not submitted last month. Corrective Action: A sample of pool water is required to be submitted each month for bacteriological analysis. |