Inspection Information:
Facility Type: | Hot Tub/Therapeutic Pool (<19 sq.m) |
Inspection type: | Follow-Up |
Inspection date: | June 23, 2014 |
Follow-up Required: | Yes |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Chlorine (Total) |
Chlorine (Free Available) 1.8ppm |
Chlorine (Combined) |
Bromine (Free Available) |
pH 7.8 |
Total Alkalinity 71 mg/L CaCo3 |
Total Hardness 65 mg/L CaCo3 |
Temperature 37°C |
Clarity clear |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
104 | Improper Turnover of Flow Rate Observation: -Flow rate measured 25 GPM. Sand filter differential pressure measure 14 psi. Indadequate Flow Rate. Hot tub is designed with a minimum flow rate of 35GPM. consult your pool engineer or architect. Corrective Action: |
203 | Inadequate or Lack of up-to-date Pool Safety Plan Observation: -Inadequate Pool Safety Plan: Pool safety Plan lacks procedure for emergency response, operating procedures for the pool and proper cleaning and maintenance directions and frequency. Corrective Action: Contact your local Environmental Health Officer if you have any questions. Submit your plans to your local EHO for approval. |
206 | Inadequate or Lack of Posted Rules and/orSignage Observation: -Inadequate signage. Corrective Action: -Pool Rules must include the following rule indicating: Patrons are prohibited from entering pool with an illness inlcuding open sores, bandages, head colds, discharging ears or noses, or infected eyes. |
401 | Note Violation Observation: -REPEAT: -Floating weir is not operational. Weir observed completely submerged below water line, not floating. Corrective Action: Repair or replace |