Inspection Information:
Facility Type: | Hot Tub/Therapeutic Pool (<19 sq.m) |
Inspection type: | Follow-Up |
Inspection date: | February 21, 2006 |
Follow-up Required: | Yes |
This facility was given a high hazard rating.
More information on hazard ratings.
Chlorine (Total) 1 |
Chlorine (Free Available) 0 |
Chlorine (Combined) |
Bromine (Free Available) |
pH >8.0 |
Total Alkalinity |
Total Hardness |
Temperature |
Clarity Good |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
401 | Critical Inadequate concentration of disinfectant Observation: No free available chlorine is detected in pool water. Corrective Action: A minimum of 1ppm free available chlorine must be maintained in the water at all times while in operation. Recommend maintaining free chlorine residual between 3 - 5ppm. |
402 | Critical Inadequate pH controls Observation: pH is measured to be greater than 8.0. Corrective Action: pH is to be maintained between 7.4 - 7.8 at all times while the pool is in operation. |
414 | Repeat Lack of automatic disinfection equipment Observation: Floating erosion feeder only. Corrective Action: A system of automatic disinfection is required. |