Bulkley Valley Regional Pool - Hot Tub - Inspection Report

Inspection Information:
Facility Type:  Hot Tub/Therapeutic Pool (<19 sq.m)
Inspection type:  Routine
Inspection date:  June 25, 2008
Follow-up Required:  Yes

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
4.2ppm
Chlorine (Free Available)
3.4 ppm
Chlorine (Combined)
Bromine (Free Available)
.8ppm = this is creeping high, please monitor.
pH
7.6
Total Alkalinity
50 ppm=this is creeping low, please monitor
Total Hardness
180 ppm
Temperature
39.4°C
Clarity
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
417   Inadequate maintenance of pool equipment
Observation: 2 Weirs near window are missing/broken off.
Corrective Action: Replace the weirs, as they help with skimming action for surface contaminants. Please complete before fall 2008