Aspen Motor Inn - Swimming Pool - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Routine
Inspection date:  November 22, 2006
Follow-up Required:  Yes

This facility was given a high hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
4.0
Chlorine (Free Available)
3.0
Chlorine (Combined)
Bromine (Free Available)
pH
>8.0
Total Alkalinity
110ppm
Total Hardness
Temperature
Clarity
Good
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
402  Critical Repeat Inadequate pH controls
Observation: pH is measured to be 8.0 or higher.
Corrective Action: pH is to be maintained within the range of 7.2 - 7.8 at all times while the pool is in operation. Adjust the pH of the pool water so that is falls within the proper range.
420   Inadequate daily maintenance records
Observation: Concentration of free available chlorine and pH are not being monitored and recorded every 4 hours as required.
Corrective Action: To be completed immediately.