Inspection Information:
Facility Type: | Hot Tub/Therapeutic Pool (<19 sq.m) |
Inspection type: | Follow-Up |
Inspection date: | March 02, 2007 |
Follow-up Required: | Yes |
This facility was given a low hazard rating.
More information on hazard ratings.
Chlorine (Total) 6.9 |
Chlorine (Free Available) 5.3 |
Chlorine (Combined) |
Bromine (Free Available) |
pH 7.1 |
Total Alkalinity 60ppm |
Total Hardness |
Temperature |
Clarity Good |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
416 | Inadequate water testing equipment Observation: Pool testing equipment is not providing accurate results. Corrective Action: Obtain a new test kit to monitor chlorine residuals and pH. The recommended kit provides accurate results to within 0.2ppm or 0.5ppm for chlorine residual testing and does not rely on a color comparison. |
421 | Other (specify below) Observation: Total alkalinity is measured to be 60ppm. The recommended range is 80 - 120ppm. Corrective Action: Increase total alkalinity to 80ppm. Low total alkalinity can contribute to pH bounce. |
421 | Other (specify below) Observation: A sample of pool water was not submitted last month for bacteriological analysis. Corrective Action: A sample of pool water is required to be submitted to the Smithers Health Unit each month for bacteriological analysis. |