Facility Location:
1 Lawson Road
Telkwa, V0J 2N0
Facility Information:
Facility Type: | 1 Public Connection |
Current Hazard Rating: | Low |
This facility is currently under a Boil Water Notice
Underlying Problems: Shallow well with only one form of treatment. Treatment system may require assessment. Result received from sample taken on Aug 22, 2023 showed present of 102 Total Coliforms. Operator has stated that the Ultraviolet treatment is working effectively. | |
Steps Taken to Remedy: - Emergency Response Contingency Plan activated. - Notification or signage posted on all taps. | |
Corrective Actions Remaining: - Shock chlorinate well and distribution system. - Two satisfactory bacteriological water sample results, showing absence of total coliforms and E. coli, taken at least 24 hours apart must be provided. - An up-to-date Emergency Response Plan must be available and provided to the Environmental Health Officer. - An assessment of the existing treatment is strongly suggested prior to removal of the Boil Water Notice. |
Facility Inspection History:
Click on an inspection link below to see additional details
Document Type | Details | |
Sample Range Report | 1-Jan-2013 to 31-Dec-2017 | |
Routine Inspection | 16-Oct-2017 | Low |
Sample Range Report | 1-Jul-2017 to 30-Sep-2017 | |
Sample Range Report | 1-Jan-2017 to 31-Mar-2017 | |
Routine Inspection | 17-Oct-2016 | Low |
Sample Range Report | 1-Jul-2016 to 30-Sep-2016 | |
Routine Inspection | 22-Sep-2015 | Low |
Routine Inspection | 8-Oct-2014 | Low |
Routine Inspection | 26-Oct-2012 | Low |
Initial Inspection | 2-Sep-2009 | Low |