Facility Location:
Naden Harbour
North Coast Regional District, V4K 5B9
Facility Information:
Facility Type: | 2-14 Connections |
Current Hazard Rating: | Unknown |
This facility is currently under a Boil Water Notice
Underlying Problems: Suspect surface water intrusion. | |
Steps Taken to Remedy: Instituted a Boil Water Notice for the system - Signage provided at all outlets. - System water is not used for drinking. Bottled water provided at all locations. | |
Corrective Actions Remaining: 1. Isolate the wells and determine if one/ both wells/distribution mains only are contaminated 2. Shock chlorinate and flush suspected mains 3. Examine the water system for points of intrusion and weakness 4. Resample. The BWN is to remain in place until two consecutive water samples are negative for Total Coliforms and E.coli taken at least 24 hours apart. |
Facility Inspection History:
Click on an inspection link below to see additional details
Document Type | Details | |
Sample Range Report | 1-Jan-2013 to 31-Dec-2017 | |
Sample Range Report | 1-Jul-2017 to 30-Sep-2017 | |
Sample Range Report | 1-Apr-2017 to 30-Jun-2017 | |
Sample Range Report | 1-Jan-2017 to 31-Mar-2017 | |
Follow-Up Inspection | 18-Jul-2008 | Low |
Routine Inspection | 16-Jun-2008 | Moderate |
Routine Inspection | 28-May-2007 | Moderate |
Routine Inspection | 22-Jul-2006 | Low |
Routine Inspection | 18-Jun-2002 | Moderate |