Seymour Lake Water System - Inspection Report

Inspection Information:
Facility Type:  WS3
Inspection type:  Routine
Inspection date:  June 09, 2017
Follow-up Required:  Yes

This facility was given a high hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
313  Critical Inadequate treatment
Observation: Water from this source is considered to be surface water and treatment is required
Corrective Action: Two forms of treatment are required that meet the surface water treatment objectives supported by the Province and Northern Health. A long term improvement plan for this system is required by 2018. This plan will assign next steps for action that will include either plans for treatment and proposed dates for completion or plans to assess the current system, by an approved professional, to determine next steps for treatment in the future. It is expected that if the water users community cannot come up with a solution, in consultation with the Health Authority, then a professional is to be contracted to provide potential solutions to the water users community.
320   Other (specify below)
Observation: Operator must successfully complete an approved Small Water System training course
Corrective Action: This is to be completed by November 2017. Contact is required with the Environmental Health Officer once registered and a copy of certificate provided upon completion.