Lakeview MHP - Inspection Report

Inspection Information:
Facility Type:  WS2
Inspection type:  Routine
Inspection date:  March 22, 2011
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
313   Inadequate treatment
Observation: Filtration - system currently employs use of 20 mm filters which is inadequate for treating water prior to UV disinfection.
Corrective Action: Immediately employ filters of at least 5 mm in size or less. Recommend putting in place coarser filters upstream (for example > 20 mm) to increase service life of the smaller filter pore sizes.