Lakeview MHP - Inspection Report

Inspection Information:
Facility Type:  WS2
Inspection type:  Follow-Up
Inspection date:  July 14, 2011
Follow-up Required:  Yes

This facility was given a high hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
313   Inadequate treatment
Observation: Operator determined that cause of flashing lights for lights 5 & 6 as noted on July 12 inspection was due to faulty ballast and therefore lamps 5 & 6 may not be producing UV.
Corrective Action: In consideration of unsatisfactory bacti results, by chlorine levels and 2 of 8 UV lamps not operable, Boil Water Notice issued on July 14, 2011.