Granisle CWS - Inspection Report

Inspection Information:
Facility Type:  WS2
Inspection type:  Routine
Inspection date:  March 13, 2023
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
320   Other (specify below)
Observation: Permit condition outline that the Direct Integrity Testing (DIT) needs to be done at least once every 7 days and 24 hours after maintenance. During the inspection it was reported that the DIT was only being done a few times a year. Operator indicated that the DIT was conducted by an external contractor.
Corrective Action: Operator needs to be trained to be able to conduct DIT with staff on site to meet the frequency requirements in the operating permit.