HI Lakeview MHP - Inspection Report

Inspection Information:
Facility Type:  WS2
Inspection type:  Routine
Inspection date:  July 12, 2011
Follow-up Required:  Yes

This facility was given a high hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
311  Critical Other (specify below)
Observation: Inspection in response to all three July 7, 2011 samples being positive for total coliform - Site 16 -STC; Site 37-STC; Site 17-GTC. Met with operator for inspection of the system. Noted that on UV monitor lights for lamps 5 and 6 were flashing on and off. Operator reports just having replaced one of these bulbs.
Corrective Action: Operator determined that cause of flashing lights for 5 and 6 as noted in July 12 inspection was due to faulty ballast and therefore lamps 5 and 6 may not be producing UV.
313   Inadequate treatment
Observation: Residual chlorine tested at three points in distribution system - trace amounts detected, ~0.04 free chlorine.
Corrective Action: Bacteriological sampler collected by EHO from Site 16, 17 and 37. Boil Water Notice pending outcome of July 12 samples. July 14, 2011 - EHO contacted BCCDC for verbal results - Site 17 10 TC; Sit 16, 37 L1/100ml. July 14, 2011 - EHO contacted operator to provide results - learned that chlorine levels in distribution very low again.