Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | August 11, 2021 |
Follow-up Required: | Yes |
This facility was given a high hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
316 | Source unprotected and subject to contamination Observation: The water well is located within 30 meters of the sewage holding tank and assumed sewage dispersal area. The sewage tank appears to be fouling, and there is a strong odour coming form it. Corrective Action: Move or repair the sewage system so it is not a potential contamination for the water. |
318 | Inadequate Microbiological Analysis data Observation: Microbiologically water samples have not been submitted for analysis since August 2020. Corrective Action: Submit monthly samples to the lab for testing. These can be done on any week of the month. |
320 | Other (specify below) Observation: The operators do not have a written emergency response plan or operational plan for the water system Corrective Action: Create an ERP and operational plan, and submit a copy to the health unit. |