Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Routine |
Inspection date: | March 04, 2010 |
Follow-up Required: | Yes |
This facility was given a high hazard rating.
More information on hazard ratings.
Chlorine (Total) >3.5 ppm |
Chlorine (Free Available) >3.5 ppm |
Chlorine (Combined) |
Bromine (Free Available) |
pH 8.0 |
Total Alkalinity |
Total Hardness |
Temperature 14°C |
Clarity |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
402 | Critical Inadequate pH controls Observation: pH is 8.0 Corrective Action: Adjust and maintain the pH below 7.8. Preferred range |
408 | Critical Lack of required safety equipment Observation: The life ring line is knotted and short. Corrective Action: Ensure the line is always free of knots and tangles and long enough to throw across the pool. |
414 | Lack of automatic disinfection equipment Observation: The automatic chlorine injector is not being used. Staff broadcast chlorine as the TAC/FAC dips. Corrective Action: Repair the automatic injection system. Close the pool until it is repaired. Do not open until consulting with the EHO. |
415 | Inadequate water turnover rate Observation: The circulation pump is shut-off and when turned on did not circulate the water. Corrective Action: Never turn the circulation pump off except for repairs and maintenance. |