Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Routine |
Inspection date: | September 18, 2017 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Chlorine (Total) |
Chlorine (Free Available) 3.6 ppm |
Chlorine (Combined) |
Bromine (Free Available) N/A |
pH 7.4 |
Total Alkalinity 50 ppm |
Total Hardness N/A |
Temperature 24 degrees C |
Clarity Acceptable |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
101 | Improper Water Chemistry/Water Clarity Observation: Total alkalinity measured at 50 ppm. TA must be maintained between 80-120 ppm. Corrective Action: Ensure TA is raised to, and maintained between 80-120 ppm. |
101 | Improper Water Chemistry/Water Clarity Observation: Total alkalinity measured at 50 ppm. TA must be maintained between 80-120 ppm. Corrective Action: Ensure TA is raised to, and maintained between 80-120 ppm. |