Trend Mountain Hotel & Conference Centre - Hot Tub - Inspection Report

Inspection Information:
Facility Type:  Hot Tub/Therapeutic Pool (<19 sq.m)
Inspection type:  Routine
Inspection date:  October 23, 2019
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
Chlorine (Free Available)
3.2
Chlorine (Combined)
Bromine (Free Available)
pH
7.0
Total Alkalinity
40
Total Hardness
Temperature
38,6C
Clarity
Clear
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Observed Total Alkalinity to be at 40ppm, pH at 7.0ppm.
Corrective Action: Ensure that the Total alkalinity is maintained at the range of 80-120ppm and pH is between 7.2-7.4ppm.
208   Improper Maintenance of Records
Observation: Observed no testing completed for Total Alkalinity in the records.
Corrective Action: Ensure that Total alkalinity is tested weekly as required and is a minimum of 80ppm - ideal range is 80-120ppm.