Sam Lindsay Memorial Centre - Teaching Pool - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Routine
Inspection date:  October 01, 2018
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
4.71 ppm
Chlorine (Free Available)
3.92 ppm
Chlorine (Combined)
Bromine (Free Available)
N/A
pH
7.57
Total Alkalinity
<10 ppm
Total Hardness
N/A
Temperature
30.7 C
Clarity
good;clear
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Repeat Improper Water Chemistry/Water Clarity
Observation: Total alkalinity measured to be <10 ppm at the time of inspection.
Corrective Action: Pool operator is aware of the low alkalinity level as they had conducted a chemistry check earlier in the day, and will be adjusting the alkalinity later in the afternoon. Total alkalinity should be maintained between 80-120 ppm to prevent rapid fluctuations in pH, possibly corrosion problems, and/or eye and skin irritation.
101   Repeat Improper Water Chemistry/Water Clarity
Observation: Total alkalinity measured to be <10 ppm at the time of inspection.
Corrective Action: Pool operator is aware of the low alkalinity level as they had conducted a chemistry check earlier in the day, and will be adjusting the alkalinity later in the afternoon. Total alkalinity should be maintained between 80-120 ppm to prevent rapid fluctuations in pH, possibly corrosion problems, and/or eye and skin irritation.