Pomeroy Hotel (FSJ) Swimming Pool - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Routine
Inspection date:  June 22, 2022
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
3.2
Chlorine (Free Available)
2.4
Chlorine (Combined)
Bromine (Free Available)
pH
7.7
Total Alkalinity
110
Total Hardness
Temperature
31.0
Clarity
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
104   Improper Turnover of Flow Rate
Observation: Flow rate (FR) reading is 47.6 gpm which is lower than the designed flow rate of 61.28 gpm
Corrective Action: Determine why FR is low and adjust it so it is meeting the designed FR
401   Note Violation
Observation: Weirs are still not installed. This is a repeated violation
Corrective Action: Install weirs