Ramada Hotel Swimming Pool - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Follow-Up
Inspection date:  November 17, 2022
Follow-up Required:  Yes

This facility was given a moderate hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
3.09 ppm
Chlorine (Free Available)
1.98 ppm
Chlorine (Combined)
Bromine (Free Available)
pH
8.12
Total Alkalinity
100 ppm
Total Hardness
Temperature
27 C
Clarity
clear
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Combined chlorine and pH were measured outside the regulatory requirements. Public Health significance - High pH and combined chlorine can cause irritation and reduce the effectiveness of disinfectants.
Corrective Action: Adjust the water chemistry so that the combined chlorine and pH are within the regulatory requirements. Patrons should not be allowed into the pool until this has been completed.