Pomeroy Hotel (FSJ) Hot Tub - Inspection Report

Inspection Information:
Facility Type:  Hot Tub/Therapeutic Pool (<19 sq.m)
Inspection type:  Routine
Inspection date:  March 24, 2017
Follow-up Required:  Yes

This facility was given a moderate hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
1.4
Chlorine (Free Available)
0.8
Chlorine (Combined)
Bromine (Free Available)
-
pH
<7.0
Total Alkalinity
100
Total Hardness
-
Temperature
39.4
Clarity
clear
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Detected free available chlorine in water is 2.8 parts per million. It does not meet requirements of pool regulation.
Corrective Action: Corrected during inspection. Added chlorine disinfectant manually to circulation system to ensure sufficient free available chlorine. Ensure that pool water chemistry parameters are regularly monitored at least 2 times a day - or once a week for alkalinity - to ensure chemistry compliance.
101  Critical Improper Water Chemistry/Water Clarity
Observation: Detected pH of pool water is below 7.0 which does not meet BC pool regulation section 10 requirements. Corrected during inspection. And sure pH is between 7.2 and 7.8 at all times.
Corrective Action: Staff added chemical to system so that final pH reached at least 7.2
104   Improper Turnover of Flow Rate
Observation: Measured flow rate 46.0 gallons per minute is above design flow rate 39.25 gallons per minute at time of inspection
Corrective Action: Please adjust flow rate so that it is similar to design flow rate by March 27th, 2017. Please monitor flow rate regularly and adjust as needed.
307   Improper Storage of Chemicals
Observation: Overall chemicals are stored in a safe manner. Thank you. However sodium bisulfate storage beside hypochlorite which is incompatible storage.
Corrective Action: Corrected during inspection. Operator transferred bisulfate to another room. Please continue to ensure chemicals are stored in a safe manner. Follow instructions on the packaging.
401   Note Violation
Observation: Detected temperature of hot water from sink tap is 52.0 °C
Corrective Action: Please maintain hot water and facility below 49 degrees Celsius. Correct by March 27th, 2017. Ensure water temperature from Taps and shower heads are merely maintained and monitored as part of Maintenance procedures.
101   Improper Water Chemistry/Water Clarity
Observation: Detected free available chlorine in water is 2.8 parts per million. It does not meet requirements of pool regulation.
Corrective Action: Corrected during inspection. Added chlorine disinfectant manually to circulation system to ensure sufficient free available chlorine. Ensure that pool water chemistry parameters are regularly monitored at least 2 times a day - or once a week for alkalinity - to ensure chemistry compliance.
101  Critical Improper Water Chemistry/Water Clarity
Observation: Detected pH of pool water is below 7.0 which does not meet BC pool regulation section 10 requirements. Corrected during inspection. And sure pH is between 7.2 and 7.8 at all times.
Corrective Action: Staff added chemical to system so that final pH reached at least 7.2
104   Improper Turnover of Flow Rate
Observation: Measured flow rate 46.0 gallons per minute is above design flow rate 39.25 gallons per minute at time of inspection
Corrective Action: Please adjust flow rate so that it is similar to design flow rate by March 27th, 2017. Please monitor flow rate regularly and adjust as needed.
307   Improper Storage of Chemicals
Observation: Overall chemicals are stored in a safe manner. Thank you. However sodium bisulfate storage beside hypochlorite which is incompatible storage.
Corrective Action: Corrected during inspection. Operator transferred bisulfate to another room. Please continue to ensure chemicals are stored in a safe manner. Follow instructions on the packaging.
401   Note Violation
Observation: Detected temperature of hot water from sink tap is 52.0 °C
Corrective Action: Please maintain hot water and facility below 49 degrees Celsius. Correct by March 27th, 2017. Ensure water temperature from Taps and shower heads are merely maintained and monitored as part of Maintenance procedures.