Houston Leisure Facility - Leisure Pool - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Routine
Inspection date:  June 23, 2017
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
4.21ppm
Chlorine (Free Available)
2.59ppm
Chlorine (Combined)
Bromine (Free Available)
pH
7.7
Total Alkalinity
117ppm CaCO3
Total Hardness
Temperature
33.5C
Clarity
Main Drains Clearly Visible
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Combined chlorine concentration exceeded 1.0ppm.
Corrective Action: Combined chlorine concentration must be maintained below 1.0ppm. Close pool immediately. Breakpoint chlorinate as soon as possible. Before reopening, rebalance pool and verify proper water chemistry parameters. If CAC concentrations often exceed 1.0ppm, then consider upgrading treatment system to include UV, or consider using an oxidizing chemical (eg. Potassium Monopersulfate). Approval from the local Environmental Health Officer must be granted before any significant changes are made to the treatment system. Pool closure confirmed. Retested pool FAC/TAC after one hour (without any reported addition of chemicals), CAC levels measured below 1.0ppm according to operator's test kit. Our test kit showed CAC concentrations at 1.5ppm. Operator was permitted to reopen the pool until the end of the day.