Inspection Information:
Facility Type: | Hot Tub/Therapeutic Pool (<19 sq.m) |
Inspection type: | Follow-Up |
Inspection date: | June 25, 2018 |
Follow-up Required: | Yes |
This facility was given a low hazard rating.
More information on hazard ratings.
Chlorine (Total) 4.76 |
Chlorine (Free Available) 3.20 |
Chlorine (Combined) |
Bromine (Free Available) |
pH 8.0 |
Total Alkalinity 57 |
Total Hardness |
Temperature |
Clarity |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
101 | Improper Water Chemistry/Water Clarity Observation: Combined chlorine was 1.56ppm, which is higher than the regulatory limit of 0.5ppm. pH was 8.0, which was higher than the regulatory prescription of 7.2 to 7.8. Total alkalinity was 57ppm, which was lower than the regulatory prescription of 80ppm to 120ppm. Corrective Action: Ensure that combined chlorine is less than 0.5ppm, pH is between 7.2 to 7.8, and that total alkalinity is between 80ppm to 120ppm. |
101 | Improper Water Chemistry/Water Clarity Observation: Combined chlorine was 1.56ppm, which is higher than the regulatory limit of 0.5ppm. pH was 8.0, which was higher than the regulatory prescription of 7.2 to 7.8. Total alkalinity was 57ppm, which was lower than the regulatory prescription of 80ppm to 120ppm. Corrective Action: Ensure that combined chlorine is less than 0.5ppm, pH is between 7.2 to 7.8, and that total alkalinity is between 80ppm to 120ppm. |