Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Routine |
Inspection date: | August 16, 2022 |
Follow-up Required: | Yes |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Chlorine (Total) 3.34 |
Chlorine (Free Available) 1.97 |
Chlorine (Combined) |
Bromine (Free Available) |
pH 7.93 |
Total Alkalinity 120 |
Total Hardness |
Temperature 27°C |
Clarity Good |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
101 | Improper Water Chemistry/Water Clarity Observation: Combined chlorine more than 1 ppm. High levels of combined chlorine can cause skin and respiratory irritation in swimmers. Regulations require combined chlorine to be less than 1 ppm. Corrective Action: Drain and dilute the pool or use the superchlorination method to reduce the combined chlorine levels of the pool. |
101 | Repeat Improper Water Chemistry/Water Clarity Observation: pH at 7.93, which is slightly higher than the regulatory maximum of 7.8. Ensure the pool pH is between 7.2 - 7.8 to ensure chlorine effectiveness and swimmer comfort. Corrective Action: Adjust pH to be between 7.2 - 7.8. |
104 | Improper Turnover of Flow Rate Observation: Flow rate meter not working at the time of inspection. High flow rates can cause the sand in the filters to be pulled into the pool. The pool had sand visible at the basin. Corrective Action: Repair the flow meter and confirm that the flow of the pool is at the designed flow rate. |
203 | Inadequate or Lack of up-to-date Pool Safety Plan Observation: No pool safety plan or data sheet readily available at the time of inspection. Corrective Action: Complete the provided templates and have a copy readily available on-site for reference. |