Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Routine |
Inspection date: | November 05, 2009 |
Follow-up Required: | Yes |
This facility was given a high hazard rating.
More information on hazard ratings.
Chlorine (Total) 3.3 ppm |
Chlorine (Free Available) 3.0 ppm |
Chlorine (Combined) |
Bromine (Free Available) |
pH 8.2 |
Total Alkalinity |
Total Hardness |
Temperature 30°C. |
Clarity Clear |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
402 | Critical Inadequate pH controls Observation: pH = 8.2. Corrective Action: Close the pool until pH is maintained = 7.8. |
413 | Critical Other (specify below) Observation: Water sampling results not received since 2003. Corrective Action: Provide bacterial samples monthly. |
414 | Lack of automatic disinfection equipment Observation: The automatic chlorine injection equipment is not being used. Instead chlorine is manually added to the pool. Corrective Action: Begin using the chlorine injection equipment before re-opening. Ensure the chlorine added is not stabilized with cyanuric acid. If you decide to use a different injection system, submit the plans for approval before purchasing any new equipment. |
417 | Inadequate maintenance of pool equipment Observation: The base of the deep ladder is broken and could be a safety hazard for feet. Corrective Action: Replace the rung as soon as possible. |
420 | Inadequate daily maintenance records Observation: Logs are up-to-date, but logged problems are not responded to. Corrective Action: Deal with problems as they arise and record how. |