Sam Lindsay Memorial Centre - Leisure Pool/Water Slide - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Routine
Inspection date:  January 22, 2018
Follow-up Required:  No

This facility was given a moderate hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
9.25 ppm
Chlorine (Free Available)
7.47 ppm
Chlorine (Combined)
Bromine (Free Available)
pH
7.58
Total Alkalinity
53 ppm
Total Hardness
Temperature
31.2C
Clarity
Clear
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Total alkalinity measured to be 53 ppm at the time of inspection.
Corrective Action: Ensure total alkalinity of the pool is maintained between 80-120 ppm to prevent rapid fluctuations in pH, possible corrosion problems, and/or eye and skin irritation.
101   Improper Water Chemistry/Water Clarity
Observation: Combined Available Chlorine was measured to be 1.78 ppm at the time of inspection.
Corrective Action: Ensure Combined Available Chlorine of the pool is maintained below 1 ppm to prevent a strong chlorine odour and/or skin and eye irritation.
101   Improper Water Chemistry/Water Clarity
Observation: Total alkalinity measured to be 53 ppm at the time of inspection.
Corrective Action: Ensure total alkalinity of the pool is maintained between 80-120 ppm to prevent rapid fluctuations in pH, possible corrosion problems, and/or eye and skin irritation.
101   Improper Water Chemistry/Water Clarity
Observation: Combined Available Chlorine was measured to be 1.78 ppm at the time of inspection.
Corrective Action: Ensure Combined Available Chlorine of the pool is maintained below 1 ppm to prevent a strong chlorine odour and/or skin and eye irritation.