Pomeroy Hotel (FSJ) Swimming Pool - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Routine
Inspection date:  January 18, 2018
Follow-up Required:  Yes

This facility was given a moderate hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
1.0
Chlorine (Free Available)
1.0
Chlorine (Combined)
Bromine (Free Available)
pH
7.6
Total Alkalinity
100
Total Hardness
Temperature
31.9 degrees C
Clarity
satisfactory
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Water temp is greater than 30 degrees C but the free chlorine only at 1.0 ppm.
Corrective Action: Minimum of 1.5 ppm free chlorine is required when the temp is greater than 30 degrees C. Raise free chlorine levels immediately. Ideal range is 1.5 -.0 ppm.
401   Note Violation
Observation: Flow meter not working.
Corrective Action: Fix or replace flow meter so that they display a reading for the flow rate. Without a working flow meter, it is impossible to determine the flow water through the filters.
101   Improper Water Chemistry/Water Clarity
Observation: Water temp is greater than 30 degrees C but the free chlorine only at 1.0 ppm.
Corrective Action: Minimum of 1.5 ppm free chlorine is required when the temp is greater than 30 degrees C. Raise free chlorine levels immediately. Ideal range is 1.5 -.0 ppm.
401   Note Violation
Observation: Flow meter not working.
Corrective Action: Fix or replace flow meter so that they display a reading for the flow rate. Without a working flow meter, it is impossible to determine the flow water through the filters.