Inspection Information:
Facility Type: | Hot Tub/Therapeutic Pool (<19 sq.m) |
Inspection type: | Routine |
Inspection date: | April 18, 2024 |
Follow-up Required: | Yes |
This facility was given a low hazard rating.
More information on hazard ratings.
Chlorine (Total) 6.18 |
Chlorine (Free Available) 4.24 |
Chlorine (Combined) |
Bromine (Free Available) |
pH 7.74 |
Total Alkalinity 74 |
Total Hardness |
Temperature 40.3°C |
Clarity Clear |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
101 | Repeat Improper Water Chemistry/Water Clarity Observation: Combine chlorine and total alkalinity does not meet legislation requirements. Combine chlorine needs to be less than 1 ppm and total alkalinity should be between 80 ppm to 120 ppm. Improper chemical levels lead to skin/eye irritation and harmful microbial growth in water. Corrective Action: Operator to adjust pool chemistry. Reduce combine chlorine to less than 1 ppm and increase alkalinity to 80 to 120 ppm. |
203 | Inadequate or Lack of up-to-date Pool Safety Plan Observation: Operator pool safety plan lacks procedure to handle fecal incidents in pool water. Fecal incident can result in contamination of pool water with pathogenic bacteria, proper disinfection is required to eliminate these bacteria. Corrective Action: Operator to update pool safety plan to include protocol for handling fecal incidents. |