Pomeroy Hotel (FSJ) Hot Tub - Inspection Report

Inspection Information:
Facility Type:  Hot Tub/Therapeutic Pool (<19 sq.m)
Inspection type:  Routine
Inspection date:  April 13, 2016
Follow-up Required:  Yes

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
Chlorine (Free Available)
0.99 ppm
Chlorine (Combined)
Bromine (Free Available)
pH
7.13
Total Alkalinity
110 ppm
Total Hardness
Temperature
39.3°C
Clarity
clear
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Ensure pool water quality adheres the minimum required levels.
Corrective Action: Refer to section 10 of pool regulation BC and schedule 3 - disinfectants. FAC, CAC and PH were unsatisfactory.
104   Improper Turnover of Flow Rate
Observation: Ensure pool re-circulation system is operating at designed flow rate 39.25 I.gpm. Actual flow rate detected was .54 I.gpm. Actual flow rate exceeding design flow rate may pose a suction hazard.
Corrective Action: There as no suction hazard based on on calculation of water velocity passing through maindrain.
101   Improper Water Chemistry/Water Clarity
Observation: Ensure pool water quality adheres the minimum required levels.
Corrective Action: Refer to section 10 of pool regulation BC and schedule 3 - disinfectants. FAC, CAC and PH were unsatisfactory.
104   Improper Turnover of Flow Rate
Observation: Ensure pool re-circulation system is operating at designed flow rate 39.25 I.gpm. Actual flow rate detected was .54 I.gpm. Actual flow rate exceeding design flow rate may pose a suction hazard.
Corrective Action: There as no suction hazard based on on calculation of water velocity passing through maindrain.