Prince George Pomeroy Inn & Suites - Inspection Report

Inspection Information:
Facility Type:  Hot Tub/Therapeutic Pool (<19 sq.m)
Inspection type:  Routine
Inspection date:  July 22, 2020
Follow-up Required:  Yes

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
2.59ppm
Chlorine (Free Available)
1.27ppm (3ppm ~ 5ppm)
Chlorine (Combined)
Bromine (Free Available)
pH
7.27 (7.2 ~ 7.8)
Total Alkalinity
60ppm (80ppm ~ 120ppm)
Total Hardness
Temperature
104F ( maximum 104F)
Clarity
main drains can be seen clearly
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Free chlorine was1.27ppm. Combined chlorine was 1.32ppm > 1ppm
Corrective Action: Ensure Free chlorine is at 3ppm ~ 5 ppm range and combined chlorine is less than 1ppm so free available chlorine will be able to work efficiently and kill the pathogenic bacteria (contaminates)