PG Aquatic Centre Leisure Pool - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Routine
Inspection date:  May 03, 2016
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
Chlorine (Free Available)
2.54
Chlorine (Combined)
Bromine (Free Available)
pH
7.80
Total Alkalinity
40
Total Hardness
Temperature
30
Clarity
Satisfactory
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Alkalinity measured to be 40 ppm. Alkalinity should be maintained within the regulated value of 80-120 ppm to ensure buffering occurs for the pH (to ensure no sudden change in pH occurs).
Corrective Action: Increase alkalinity to 80 ppm.
401   Note Violation
Observation: Digital flow meter is broken. Existing manual flow meters are in areas which make them difficult to read. Knowing the accurate flow rate is necessary for ensuring proper turn over rate.
Corrective Action: Fix/replace broken flow meters.
101   Improper Water Chemistry/Water Clarity
Observation: Alkalinity measured to be 40 ppm. Alkalinity should be maintained within the regulated value of 80-120 ppm to ensure buffering occurs for the pH (to ensure no sudden change in pH occurs).
Corrective Action: Increase alkalinity to 80 ppm.
401   Note Violation
Observation: Digital flow meter is broken. Existing manual flow meters are in areas which make them difficult to read. Knowing the accurate flow rate is necessary for ensuring proper turn over rate.
Corrective Action: Fix/replace broken flow meters.