Sam Lindsay Memorial Centre - Leisure Pool/Water Slide - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Routine
Inspection date:  June 15, 2023
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
Chlorine (Free Available)
2.17
Chlorine (Combined)
Bromine (Free Available)
pH
7.17
Total Alkalinity
64
Total Hardness
Temperature
24.6°C
Clarity
good
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Combined chlorine concentration was 1.30 ppm which is about the acceptable limit of 1 ppm maximum. Elevated combined chlorine may cause strong odours, eye/skin irritation, and decreased free available chlorine efficacy.
Corrective Action: Operator immediately instructed staff to remeasure and balance the pool water. Staff were observed addressing the water quality. A filter backwash will also be conducted at the end of the day.