Child Development Centre Pool - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Routine
Inspection date:  April 27, 2017
Follow-up Required:  Yes

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
2.0
Chlorine (Free Available)
1.5
Chlorine (Combined)
Bromine (Free Available)
-
pH
7.3
Total Alkalinity
90
Total Hardness
-
Temperature
35.4°C
Clarity
clear - main drain visible
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
205   Improper Monitoring of Chemical Paramaters or Safety Tests
Observation: Free available chlorine (FAC), combined chlorine (CC) parameters and pH are only recorded once daily. (alkalinity is being recorded daily as shown in records – good).
Corrective Action: Frequent monitoring of chemical parameters help ensure that water chemistry is balanced. This also helps identify chemistry issues at an early stage so corrective action can occur in a timely manner. Please test and record FAC, CC and pH parameters twice daily. Operator tested chemistry with her test kit during inspection and chemistry is in compliance. This can be considered as second testing of the day.
205   Improper Monitoring of Chemical Paramaters or Safety Tests
Observation: Free available chlorine (FAC), combined chlorine (CC) parameters and pH are only recorded once daily. (alkalinity is being recorded daily as shown in records – good).
Corrective Action: Frequent monitoring of chemical parameters help ensure that water chemistry is balanced. This also helps identify chemistry issues at an early stage so corrective action can occur in a timely manner. Please test and record FAC, CC and pH parameters twice daily. Operator tested chemistry with her test kit during inspection and chemistry is in compliance. This can be considered as second testing of the day.