Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Routine |
Inspection date: | July 03, 2014 |
Follow-up Required: | Yes |
This facility was given a low hazard rating.
More information on hazard ratings.
Chlorine (Total) |
Chlorine (Free Available) 1.7ppm |
Chlorine (Combined) |
Bromine (Free Available) |
pH 76 |
Total Alkalinity 127 mg/L CaC03 |
Total Hardness |
Temperature 32°C |
Clarity Main drains clearly visable |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
101 | Critical Improper Water Chemistry/Water Clarity Observation: Combined chlorine measured 1.9ppm at time of inspection. Corrective Action: Pool was closed at time of inspection. Ensure combined chlorine concentration does not exceed 1.0ppm. Conduct breakpoint chlorination. |