Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Routine |
Inspection date: | April 13, 2016 |
Follow-up Required: | Yes |
This facility was given a low hazard rating.
More information on hazard ratings.
Chlorine (Total) |
Chlorine (Free Available) 55 ppm |
Chlorine (Combined) |
Bromine (Free Available) |
pH 7.77 |
Total Alkalinity 1.6 ppm |
Total Hardness |
Temperature 28.8°C |
Clarity Clear |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
104 | Improper Turnover of Flow Rate Observation: Ensure pool circulation system is operating at the designed flow rate. Flow rate read was 77 I.gpm. Design flow rate is 61.38 I.gpm. Actual flow rate exceeding design flow rate may pose a suction hazard. Corrective Action: There was no suction hazard based on calculation of water velocity passing through a suction point (ex. main drain). |
305 | Improper Maintenance of Pool Surface, Walkways, Floors and/or Construction Observation: Ensure there is a protective fitting around base of hand rails to prevent physical injury. Corrective Action: |
104 | Improper Turnover of Flow Rate Observation: Ensure pool circulation system is operating at the designed flow rate. Flow rate read was 77 I.gpm. Design flow rate is 61.38 I.gpm. Actual flow rate exceeding design flow rate may pose a suction hazard. Corrective Action: There was no suction hazard based on calculation of water velocity passing through a suction point (ex. main drain). |
305 | Improper Maintenance of Pool Surface, Walkways, Floors and/or Construction Observation: Ensure there is a protective fitting around base of hand rails to prevent physical injury. Corrective Action: |