Inspection Information:
Facility Type: | Hot Tub/Therapeutic Pool (<19 sq.m) |
Inspection type: | Routine |
Inspection date: | August 16, 2022 |
Follow-up Required: | Yes |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Chlorine (Total) >5 ppm |
Chlorine (Free Available) 4.46 ppm |
Chlorine (Combined) |
Bromine (Free Available) |
pH 7.94 |
Total Alkalinity 111 |
Total Hardness |
Temperature 39°C |
Clarity Good |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
101 | Improper Water Chemistry/Water Clarity Observation: pH at 7.94. pH must be between 7.2 - 7.8 to ensure chlorine effectiveness and swimmer comfort. Corrective Action: Adjust pH level to meet regulatory requirements. |
101 | Improper Water Chemistry/Water Clarity Observation: Combined chlorine level of hot tub at 1 ppm (Regulations state it must be less than 1 ppm). Combined chlorine causes respiratory and skin irritation to swimmers. Corrective Action: Reduce combined chlorine levels by draining and refilling the pool or use the superchlorination method to reduce it to regulatory range (less than 1ppm) |
203 | Inadequate or Lack of up-to-date Pool Safety Plan Observation: No pool data sheets or pool safety plan readily available. A pool safety plan and data sheet outlines the care-taking and maintenance of the pool in the event of contamination or emergency. Corrective Action: Complete the attached pool safety plan and data sheet template and provide a copy to Northern Health for filing. Have a copy available on site for reference. |
305 | Improper Maintenance of Pool Surface, Walkways, Floors and/or Construction Observation: Flow meter was not functioning at time of inspection. Flow meters determine the rate that water is circulated in the system. The flow must be at or close to the design flow rate to ensure water is treated effectively and the system is not running at a rate that can damage its components. Corrective Action: Repair and install the flow meter and ensure the flow rate is at or close to the daily designed flow rate. |