Mackenzie Leisure Services Hot Tub - Inspection Report

Inspection Information:
Facility Type:  Hot Tub/Therapeutic Pool (<19 sq.m)
Inspection type:  Routine
Inspection date:  September 13, 2007
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
Chlorine (Free Available)
Chlorine (Combined)
Bromine (Free Available)
pH
Total Alkalinity
Total Hardness
Temperature
Clarity
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
417   Inadequate maintenance of pool equipment
Observation: Weir is still missing.
Corrective Action: Please re-attach.
421   Other (specify below)
Observation: Hot Tub flow rate maintained at 62 gpm. This is too high.
Corrective Action: - Hot Tub was designed to maintain a maximum of 35 imperial gallons per minute only. - decrease the total compined flow rate (of the skimmer and main drain) to maintain 28 to 35 imperial gallons per minute.