Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Routine |
Inspection date: | May 03, 2016 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Chlorine (Total) |
Chlorine (Free Available) 2.54 |
Chlorine (Combined) |
Bromine (Free Available) |
pH 7.80 |
Total Alkalinity 40 |
Total Hardness |
Temperature 30 |
Clarity Satisfactory |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
101 | Improper Water Chemistry/Water Clarity Observation: Alkalinity measured to be 40 ppm. Alkalinity should be maintained within the regulated value of 80-120 ppm to ensure buffering occurs for the pH (to ensure no sudden change in pH occurs). Corrective Action: Increase alkalinity to 80 ppm. |
401 | Note Violation Observation: Digital flow meter is broken. Existing manual flow meters are in areas which make them difficult to read. Knowing the accurate flow rate is necessary for ensuring proper turn over rate. Corrective Action: Fix/replace broken flow meters. |
101 | Improper Water Chemistry/Water Clarity Observation: Alkalinity measured to be 40 ppm. Alkalinity should be maintained within the regulated value of 80-120 ppm to ensure buffering occurs for the pH (to ensure no sudden change in pH occurs). Corrective Action: Increase alkalinity to 80 ppm. |
401 | Note Violation Observation: Digital flow meter is broken. Existing manual flow meters are in areas which make them difficult to read. Knowing the accurate flow rate is necessary for ensuring proper turn over rate. Corrective Action: Fix/replace broken flow meters. |