Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Complaint |
Inspection date: | February 03, 2017 |
Follow-up Required: | Yes |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Chlorine (Total) 3.63 |
Chlorine (Free Available) 2.09 |
Chlorine (Combined) |
Bromine (Free Available) |
pH |
Total Alkalinity |
Total Hardness |
Temperature |
Clarity |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
101 | Improper Water Chemistry/Water Clarity Observation: Combined chlorine measured at 1.49 and 1.54 ppm. Maximimum allowable limit is 1 ppm. Corrective Action: To bring this down please superchlorinate pool to 15 ppm chlorine and maintain this concentration for 6 hours. Pool to remain closed until the chlorine dissapates and the combined chlorine is below 1ppm with the Palintest. |
101 | Improper Water Chemistry/Water Clarity Observation: Combined chlorine measured at 1.49 and 1.54 ppm. Maximimum allowable limit is 1 ppm. Corrective Action: To bring this down please superchlorinate pool to 15 ppm chlorine and maintain this concentration for 6 hours. Pool to remain closed until the chlorine dissapates and the combined chlorine is below 1ppm with the Palintest. |