Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Routine |
Inspection date: | April 30, 2018 |
Follow-up Required: | Yes |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Chlorine (Total) 9.6 |
Chlorine (Free Available) 9.2 |
Chlorine (Combined) |
Bromine (Free Available) N/A |
pH 8.4 |
Total Alkalinity 143 ppm |
Total Hardness |
Temperature 39 |
Clarity Satisfactory. Main drain cover visible |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
101 | Improper Water Chemistry/Water Clarity Observation: Main pool pH is excessively high. Chlorine disinfectant is not effective when pH is above 7.8 Corrective Action: The ideal pH is 7.4 this requires the use of a pH down products or a form of muriatic acid. Operator is draining the pool to reduce the pH because the facility ran out of pH down product. |
104 | Improper Turnover of Flow Rate Observation: Flow meter during regular operation indicates the flow rate to be inadequately low, below 40 GPM. However, it appears to be working during filer filter backwash. Corrective Action: Please check to ensure the pump is running smoothly. Operator was conducting a filter backwash during the inspection.. |
203 | Inadequate or Lack of up-to-date Pool Safety Plan Observation: Pool Safety Plan not available on site. This must be kept on site in cases where management is not available when an emergency occurs. Corrective Action: Ensure a copies are made available to the front desk and in the pool chemical room. This plan must be reviewed annually. |
101 | Improper Water Chemistry/Water Clarity Observation: Main pool pH is excessively high. Chlorine disinfectant is not effective when pH is above 7.8 Corrective Action: The ideal pH is 7.4 this requires the use of a pH down products or a form of muriatic acid. Operator is draining the pool to reduce the pH because the facility ran out of pH down product. |
104 | Improper Turnover of Flow Rate Observation: Flow meter during regular operation indicates the flow rate to be inadequately low, below 40 GPM. However, it appears to be working during filer filter backwash. Corrective Action: Please check to ensure the pump is running smoothly. Operator was conducting a filter backwash during the inspection.. |
203 | Inadequate or Lack of up-to-date Pool Safety Plan Observation: Pool Safety Plan not available on site. This must be kept on site in cases where management is not available when an emergency occurs. Corrective Action: Ensure a copies are made available to the front desk and in the pool chemical room. This plan must be reviewed annually. |