North Peace Leisure Pool (Leisure Pool) - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Routine
Inspection date:  June 17, 2022
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
5.2 ppm
Chlorine (Free Available)
4.96
Chlorine (Combined)
Bromine (Free Available)
pH
7.76
Total Alkalinity
90 mg/L
Total Hardness
Temperature
31.6
Clarity
clear
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Oxidation reduction potential (ORP) was measured at 776 mV; Maximum value is 750 mV.
Corrective Action: Adjust chemicals to ensure ORP remains within the ideal range of 700 mV - 750 mV.
305   Improper Maintenance of Pool Surface, Walkways, Floors and/or Construction
Observation: Flow meter was not operational during inspection.
Corrective Action: Flow meter should be replaced to ensure operator can calculate the turnover rate of the leisure pool.