Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Follow-Up |
Inspection date: | April 13, 2018 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Chlorine (Total) |
Chlorine (Free Available) |
Chlorine (Combined) |
Bromine (Free Available) |
pH |
Total Alkalinity |
Total Hardness |
Temperature |
Clarity |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
104 | Improper Turnover of Flow Rate Observation: Design Flow Rate (DFR) from updated the Pool Data Sheet= 478 US gpm Observed Flow Rate = 603 US gpm Velocity = 0.32 x Q (US gpm) / A (in²) = 0.32 x 603 US gpm / (37.5in² * 3) = 1.72 ft/sec Velocity through main drains are unsatisfactory. Corrective Action: Ensure recirculation pump is operating at the DFR and that the velocity through the drain openings are < 1.5 ft/sec. Flow was adjusted to 474 US gpm during inspection. |
203 | Repeat Inadequate or Lack of up-to-date Pool Safety Plan Observation: Pending updated Pool Safety Plan (PSP). Corrective Action: Send completed PSP within 1 month to EHO. |
307 | Repeat Improper Storage of Chemicals Observation: Off-site chemical room was not securely lockable. Corrective Action: Ensure door is securely locked when not in use. |
104 | Improper Turnover of Flow Rate Observation: Design Flow Rate (DFR) from updated the Pool Data Sheet= 478 US gpm Observed Flow Rate = 603 US gpm Velocity = 0.32 x Q (US gpm) / A (in²) = 0.32 x 603 US gpm / (37.5in² * 3) = 1.72 ft/sec Velocity through main drains are unsatisfactory. Corrective Action: Ensure recirculation pump is operating at the DFR and that the velocity through the drain openings are < 1.5 ft/sec. Flow was adjusted to 474 US gpm during inspection. |
203 | Repeat Inadequate or Lack of up-to-date Pool Safety Plan Observation: Pending updated Pool Safety Plan (PSP). Corrective Action: Send completed PSP within 1 month to EHO. |
307 | Repeat Improper Storage of Chemicals Observation: Off-site chemical room was not securely lockable. Corrective Action: Ensure door is securely locked when not in use. |