Sam Lindsay Memorial Centre - Teaching Pool - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Routine
Inspection date:  August 19, 2016
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
Chlorine (Free Available)
1.01 mg/L
Chlorine (Combined)
Bromine (Free Available)
pH
7.37
Total Alkalinity
30 mg/L
Total Hardness
Temperature
Clarity
Adequate
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Total alkalinity maintained at 30 ppm
Corrective Action: Ensure total alkalinity of pool is maintained in the range of 80-120 ppm to help the pool water resist rapid changes in pH
101   Improper Water Chemistry/Water Clarity
Observation: Total alkalinity maintained at 30 ppm
Corrective Action: Ensure total alkalinity of pool is maintained in the range of 80-120 ppm to help the pool water resist rapid changes in pH