Ramada Hotel Swimming Pool - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Follow-Up
Inspection date:  November 16, 2020
Follow-up Required:  Yes

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
3.96
Chlorine (Free Available)
3.68
Chlorine (Combined)
Bromine (Free Available)
pH
>8.4
Total Alkalinity
128
Total Hardness
Temperature
Clarity
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: The pH measured >8.4 and should measure between 7.2 and 7.8.
Corrective Action: Continue to assess the water chemistry and make adjustments to ensure that the pH is within the expected parameters set out in the legislation.