Inspection Information:
Facility Type: | Hot Tub/Therapeutic Pool (<19 sq.m) |
Inspection type: | Follow-Up |
Inspection date: | April 09, 2018 |
Follow-up Required: | No |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Chlorine (Total) 1.38 ppm |
Chlorine (Free Available) 1.25 ppm |
Chlorine (Combined) |
Bromine (Free Available) N/A |
pH 8.06 |
Total Alkalinity 93 ppm |
Total Hardness N/A |
Temperature 34°C |
Clarity Satisfactory. Main drain cover visible. |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
101 | Critical Improper Water Chemistry/Water Clarity Observation: Water chemistry is still out of balance. pH is excessively high at 8.06 Disinfectant level is too low at 1.25 ppm. Corrective Action: After adjustment, pool can be re-opened. |
101 | Critical Improper Water Chemistry/Water Clarity Observation: Water chemistry is still out of balance. pH is excessively high at 8.06 Disinfectant level is too low at 1.25 ppm. Corrective Action: After adjustment, pool can be re-opened. |