Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Routine |
Inspection date: | May 01, 2012 |
Follow-up Required: | Yes |
This facility was given a low hazard rating.
More information on hazard ratings.
Chlorine (Total) |
Chlorine (Free Available) 2.97 |
Chlorine (Combined) |
Bromine (Free Available) |
pH 7.78 |
Total Alkalinity 91 ppm |
Total Hardness |
Temperature >37°C |
Clarity |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
411 | Critical Improper or lack-of ground-fault interrupter Observation: Operator was unaware of the ground fault circuit interruptor and how to turn it off. Operator was advised on the ground fault interruptor at the time of inspection. Corrective Action: Ensure that the ground fault interruptor is identified and that the operator is aware of how to turn it on and off in cases of emergencies. Ground fault interruptor should be checked at least monthly to ensure that it is working properly. |
413 | Critical Other (specify below) Observation: Both skimmers lacked floating weirs. Corrective Action: Ensure floating weirs are installed for skimmers. Weirs should be floating at a 45° angle. |
420 | Inadequate daily maintenance records Observation: Combined Chlorine and Alkalinity of pool water was not tested and recorded as per the Pool Regulations. Corrective Action: Ensure combined Chlorine is tested and recorded at least twice daily. Combined Chlorine must not exceed 1 ppm. Alkalinity must be tested at least once per week. Alkalinity must be maintained between 80 and 120 ppm. |
421 | Other (specify below) Observation: Observed pooling water by waterslide. Corrective Action: Pool deck should be sloped towards the drains to avoid ponding water. |
421 | Other (specify below) Observation: Rope for throwing ring was held together with duct tape. Corrective Action: Ensure rope is replaced. |