Inspection Information:
Facility Type: | Hot Tub/Therapeutic Pool (<19 sq.m) |
Inspection type: | Routine |
Inspection date: | March 29, 2021 |
Follow-up Required: | Yes |
This facility was given a low hazard rating.
More information on hazard ratings.
Chlorine (Total) 4.76 |
Chlorine (Free Available) 4.09 |
Chlorine (Combined) |
Bromine (Free Available) |
pH 8.1 |
Total Alkalinity |
Total Hardness |
Temperature |
Clarity clear |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
104 | Improper Turnover of Flow Rate Observation: Flow meter was not working during the inspection. Corrective Action: Replace or repair the flow meter so it can be confirmed that water turns over in 30 mins. |
401 | Note Violation Observation: The Hot tub changed to a automatic disinfection system in 2017, A construction permit was asked for at this time and has yet to be submitted. Corrective Action: Submit a construction permit and pool data sheet for review. |