Pomeroy Hotel (FSJ) Swimming Pool - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Follow-Up
Inspection date:  January 19, 2018
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
1.0
Chlorine (Free Available)
1.0
Chlorine (Combined)
Bromine (Free Available)
pH
7.4
Total Alkalinity
90
Total Hardness
Temperature
33.1 degrees C
Clarity
satisfactory
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Free chlorine is only 1.0 ppm when the water temp is greater than 30 degrees C.
Corrective Action: Increase free chlorine to at least 1.5 ppm as the water temp is greater than 30 degrees C.
101   Improper Water Chemistry/Water Clarity
Observation: Free chlorine is only 1.0 ppm when the water temp is greater than 30 degrees C.
Corrective Action: Increase free chlorine to at least 1.5 ppm as the water temp is greater than 30 degrees C.