Chetwynd & District Leisure Pool Hot Tub - Inspection Report

Inspection Information:
Facility Type:  Hot Tub/Therapeutic Pool (<19 sq.m)
Inspection type:  Routine
Inspection date:  September 30, 2013
Follow-up Required:  Yes

This facility was given a low hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
Chlorine (Free Available)
3.47 ppm
Chlorine (Combined)
Bromine (Free Available)
pH
8.04
Total Alkalinity
80 ppm
Total Hardness
Temperature
105.6°F
Clarity
Good. Able to see pattern of main drain.
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Combined Available Chlorine was measured at 1.43 ppm. Combined chlorine must be less than 1 ppm at all times.
Corrective Action: Please adjust chemicals to bring combined chlorine down immediately.
101   Improper Water Chemistry/Water Clarity
Observation: pH is too high. Measured at 8.04 pH must be maintained between 7.2 -7.8 at all times.
Corrective Action: Please adjust chemicals to bring pH down to appropriate range.
103   Improper Pool Temperature
Observation: Temperature of pool water is a bit high 105.6°F (40.8°C).
Corrective Action: Temperature of hot tub water must be less than 40°C (104°F).Temperature was adjusted during inspection.
401   Note Violation
Observation: Vials used for test kit are worn out and discoloured which affects the accuracy of your results.
Corrective Action: Please replace vials as soon as possible. Please ensure all vials are rinsed out after each use to prevent discolouring in the future.
401   Note Violation
Observation: All skimmers were missing skimming devices.
Corrective Action: Please ensure a skimming device is provided as soon as possible.