Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Initial |
Inspection date: | March 26, 2018 |
Follow-up Required: | Yes |
This facility was given a low hazard rating.
More information on hazard ratings.
Chlorine (Total) 3.37 |
Chlorine (Free Available) 3.37 |
Chlorine (Combined) |
Bromine (Free Available) |
pH 7.94 |
Total Alkalinity 125 |
Total Hardness |
Temperature 31 |
Clarity Satisfactory |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
101 | Improper Water Chemistry/Water Clarity Observation: Total alkalinity measured 125ppm and pH measured 7.94. Corrective Action: Ensure chemical parameters are adjusted so that total alkalinity is maintained between 80 to 120 ppm and that pH is maintained between 7.2 to 7.8. |
305 | Improper Maintenance of Pool Surface, Walkways, Floors and/or Construction Observation: REPEAT: Both skimmers are missing weirs. Corrective Action: Ensure properly functioning weirs are installed for the skimmers to allow for proper skimming action. |
101 | Improper Water Chemistry/Water Clarity Observation: Total alkalinity measured 125ppm and pH measured 7.94. Corrective Action: Ensure chemical parameters are adjusted so that total alkalinity is maintained between 80 to 120 ppm and that pH is maintained between 7.2 to 7.8. |
305 | Improper Maintenance of Pool Surface, Walkways, Floors and/or Construction Observation: REPEAT: Both skimmers are missing weirs. Corrective Action: Ensure properly functioning weirs are installed for the skimmers to allow for proper skimming action. |